Wheelock® Exceder Series Horns, Strobes, and Horn Strobes

Modern, Efficient, and Scalable Notification Solutions

The Wheelock Exceder Series rom Kidde Fire Systemsis compatible with the AEGIS™-PHX,   ARIES™-SLX and ARIES™-MLX suppression control units. These appliances combine modern aesthetics, high reliability, and low current draw, allowing for more devices per circuit and streamlined installation.

Each unit integrates advanced optical technology for consistent illumination and audibility across a range of environments, ensuring compliance and confidence in every application.

Key Advantages
  • Multi-Candela Flexibility
    8 candela settings per device for easy on-site adjustment.
  • Adjustable Sound Output
    3 field-selectable sound levels — 90, 95, and 99 dB.
  • Universal Mounting Base
    Simplifies installation, supports pre-wire testing, and fits five backbox types.
  • Tool-Free Configuration
    Slide switches and test points allow easy setup and inspection.
  • Low Current Draw
    Reduces power demand, enabling more devices per notification appliance circuit.
  • Sleek Modern Design
    Clean, compact appearance blends seamlessly into any space.
  • Full Compatibility
    Synchronizes with Kidde Fire Systems DSM Sync Modules and AEGIS™-PHX,   ARIES™-SLX and ARIES™-MLX control units for unified signaling.

Applications

The Exceder Series is ideal for:

  • Commercial and industrial buildings requiring flexible wall or ceiling mounting
  • Facilities prioritizing energy efficiency and scalable NAC expansion
  • Locations needing ADA-compliant audible and visual alerts
  • Environments requiring synchronized, tamper-resistant signaling systems
Applications for The Exceder Series
System Architecture

Construction & Design

Housing: Flame-retardant thermoplastic with Lexan® lens for durability and clarity
Mounting: Universal base fits standard single-gang, double-gang, and 4-inch boxes
Color Options: Red or white, wall or ceiling mount variants
Label Options: “Agent” marked versions available for suppression system integration
Inspection-Friendly: Built-in voltage test points and optional locking screw for secure installation

Technical Specifications

SPECIFICATION DETAILS
Operating Voltage Range 8–33 VDC (Regulated)
Sound Levels 90 / 95 / 99 dB (Selectable)
Candela Settings (Wall) 15, 15/75, 30, 75, 95, 110, 135, 185
Candela Settings (Ceiling) 15, 30, 60, 75, 95, 115, 150, 177
Flash Rate 1 Hz (1 flash per second)
Operating Temperature 32°F to 120°F (0°C to 49°C)
Relative Humidity Up to 93%
Mounting Options 5 box types (Surface, Semi-Flush, 4″ Square, Octal, European 100mm)
Certifications UL 1971, UL 464, ULC, FM, CSFM, RoHS Compliant
Compliance & Certifications
  • UL 1971 (Emergency Devices for the Hearing Impaired)
  • UL 464 (Fire Protective Signaling)
  • ULC Listed
  • California State Fire Marshal (CSFM) Approved
  • FM Approved
  • RoHS Compliant
Resources

Data Sheet: Wheelock Exceder Notification Appliances (K-75-020)

Kidde Fire Systems Capabilities Brochure (BR101_2023)

Resource links coming soon!

Modern Design. Maximum Dependability.

The Wheelock Exceder™ Series delivers the perfect balance of form and function, ensuring every alarm is heard and seen clearly, every time. With universal mounting, flexible configuration, and a modern aesthetic, Exceder is built to simplify installation while elevating system performance.